GD Midea Refrigerant Equipment Co. Ltd Service manual for Electrolux split Series
22
Current protection
(LED indicates)
Check the indoor
air filter.
Does outdoor heat-
exchanger frosted?
No
It is normal under
that ambient temp.
Check the
drainage
system of
out door unit.
Yes
Does indoor heat-
exchanger frosted?
Yes
Check speed
of indoor
motor.
Yes
No
Does the outdoor
temp over 48 C?
o
Check the outdoor
condenser.
Does it occur in
Cool mode?
Check speed
of outdoor
motor.
Yes
Check the over-
current protector of
compressor.
No
Replace the
main PCB board.
Replace the
compressor.
Recycle the
refrigerant
and recharge.
No
Does the indoor
temp low than 10 C?
o
Yes
No
Check the s olenoid
coil of reverse valve.
Check the over-
c urrent protector of
compressor.
Replace the
main PCB board.
Recycle the refrige-
rant and recharge.
Replace the re verse
valve.
Check the position
and wiring of temp
sensor (all of the m).
If wrong, the unit will
result in current
prote ction, not temp.
C heck the soft
starter mould.
Check the soft
starter mould.
The unit does not
operate
Does the power LED
light after turning
the switch on?
Check the electrical
source.
No
Check the power
supplier.
Does the voltage
between input
terminates o f
transformer is
correct?
Does the voltage
between outp ut
terminates o f
transformer is
correct?
Does the power
transfer to the
display board?
Replace the main
PCB board.
Yes
Yes
No
Check wiring.
Replace the
transformer.
No
No
Do the LED lamps
indicates ERR?
Ye s
Perform
the related
inst ructions.
Yes
No
Is there beep from
the unit when using
remoter?
Check the soft
starter
Check the battery
of the remoter.
No
Check the display
board.
Replace the
display board.
Yes
No
Replace the
disp lay board .
Yes
Ye s
Does the unit run in
Forced Cool mode?